NF160-SGV 3P 125-160A

Materialnummer 255040
Leistungsschalter 3polig. Ir = 125 - 160A; Icu = Ics = 36kA bei AC 440V

FA-MCCB: Kompakte Leistungsschalter

SeriesWS-V SERIES - MCCB
TypeNF-S TYPE (STANDARD CLASS)
Frame Size160
Rated Current (A)125-160
Current TypeAC/DC
Number of Poles3
Rated Voltage (V)690
Breaking Capacity at 400V (kA)36/36
Compliant with Standard(s)IEC 60947-2, EN 60947-2
Cycles with Rated Current15.000
Cycles without Rated Current40.000
Automatic Tripping DeviceTHERMAL-MAGNETIC

Produktabmessungen & Gewicht

Depth (mm)92
Weight (kg)1,6
Width (mm)105
Height (mm)165

Konformität

CECOMPLIANT
Shipping ApprovalsNON-COMPLIANT
EACNON-COMPLIANT
UL/cULNON-COMPLIANT
UKCACOMPLIANT

Product Packaging

Aluminum (g)0
Others (g)0
Styrofoam (g)0
Cardboard (g)92
Steel (g)0
Glass (g)0
Other plastic (g)0
Wood (g)0
Other paper (g)0

Umwelt

REACH Limit ExceededYES
REACH Substance CAS Number119344-86-4
Dangerous Goods ClassNO
WEEEB2C
Dangerous Goods IdentifierNO