MITSUBISHI ELECTRIC Changes for the Better
Germany

Leistungsschütz. 4kW; 1S; Us = AC 200V, 50Hz

FA-MC: Leistungsschütz

SeriesMS-T SERIES MAGNETIC CONTACTOR
TypeNON-REVERSING, AC OPERATED
Frame Size10
Current TypeAC TYPE
Coil Voltage (V)200-240
Rated Current (A)3-PHASE AC690V: 5
Rated Capacity (kW)3-PHASE AC220-240V: 2.5, 3-PHASE AC380-440V: 4, 3-PHASE AC690V: 4
Rated Voltage (V)690
Number of Poles3
No of Auxiliary Contacts NO1
Frequency Range (Hz)50/60
Min. Ambient Temperature (°C)-10
Max. Ambient Temperature (°C)40
WiringSCREW-CLAMP
Design / StylingSTANDARD
Compliant with Standard(s)EN60947-4-1, IEC60947-4-1, JIS C8201-4-1
Electrical Durability (Load)100000(AT 9A;AC-3;380-440VAC)
Mech. Durability (at no Load)10 000 000 OPERATIONS
Protection ClassIP20

Produktabmessungen & Gewicht

Depth (mm)78
Weight (kg)0,25
Width (mm)36
Height (mm)75

Konformität

CECOMPLIANT
EACNON-COMPLIANT
UL/cULCOMPLIANT
UKCACOMPLIANT

Product Packaging

Aluminum (g)0
Others (g)0
Styrofoam (g)0
Cardboard (g)150
Steel (g)0
Glass (g)0
Other plastic (g)1
Wood (g)0
Other paper (g)0

Umwelt

REACH Limit ExceededNO
RoHS ComplianceCOMPLIANT
Dangerous Goods ClassNO
WEEEB2B
Dangerous Goods IdentifierNO